Backflow assembly test · Golden Market
ApprovedFiled Nov 27, 2024 by Avery Ramirez, Heritage Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Nov 27, 2024
- Assembly type
- DC
- Serial number
- K529285
- Size
- 1 1/2
- Test gauge serial
- G-5453
- Gauge calibration date
- Oct 9, 2023
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 051-69-01269
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.