Backflow assembly test · 3596 Fox Run Rd
ApprovedFiled Sep 29, 2025 by Shawn Nguyen, Valley Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Sep 29, 2025
- Assembly type
- RP
- Serial number
- W702434
- Size
- 3/4
- Test gauge serial
- G-5197
- Gauge calibration date
- Apr 3, 2025
- Check valve 1
- 5.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 051-26-01183
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.