Mono County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Station Pizza

Filed Nov 18, 2026 by Parker Nguyen, Heritage Backflow Testing · filed from phone

Report

Date of service
Nov 18, 2026
Assembly type
RP
Serial number
K715927
Size
1
Test gauge serial
G-3140
Gauge calibration date
May 30, 2026
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 051-49-01287
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

7111 Old Church Ct
Owner: Marsh Holdings LLC
Parcel 051-49-01287