Backflow assembly test · 6492 Ridgeview Way
Needs reviewFiled Nov 24, 2026 by Parker Nguyen, Heritage Backflow Testing · filed from phone
Report
- Date of service
- Nov 24, 2026
- Assembly type
- RP
- Serial number
- W112176
- Size
- 1
- Test gauge serial
- G-1746
- Gauge calibration date
- Mar 27, 2026
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 051-36-01049
- Readings in range, no flags
- Result: passing. Next due date resets when approved.