Mono County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Two Rivers Animal Hospital

Approved

Filed Jul 17, 2025 by Parker Nguyen, Heritage Backflow Testing · filed from phone

Report

Date of service
Jul 17, 2025
Assembly type
RP
Serial number
Z432179
Size
2
Test gauge serial
G-5362
Gauge calibration date
Mar 15, 2025
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 051-62-01299
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

4357 Sycamore Dr
Owner: Stroud Holdings LLC
Parcel 051-62-01299