← Backflow review queue
Backflow assembly test · Crossroads Elementary School
ApprovedFiled May 20, 2025 by Parker Nguyen, Heritage Backflow Testing · filed from phone
Report
- Date of service
- May 20, 2025
- Assembly type
- RP
- Serial number
- A363602
- Size
- 1
- Test gauge serial
- G-7460
- Gauge calibration date
- Mar 12, 2025
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 4 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 051-17-01237
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
9855 Pine Knoll Ln
Owner: Wexler Holdings LLC
Parcel 051-17-01237