Backflow assembly test · Riverside Apartments
ApprovedFiled Jan 21, 2024 by Avery Ramirez, Heritage Backflow Testing · filed from phone
Report
- Date of service
- Jan 21, 2024
- Assembly type
- DC
- Serial number
- K932306
- Size
- 2
- Test gauge serial
- G-2853
- Gauge calibration date
- Jun 23, 2023
- Check valve 1
- 3.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 051-26-01268
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6387 Quarry Ln
Owner: Marsh Holdings LLC
Parcel 051-26-01268