← Backflow review queue
Backflow assembly test · 2706 Cedar Hollow Ln
ApprovedFiled May 27, 2024 by Parker Ashby, Valley Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- May 27, 2024
- Assembly type
- RP
- Serial number
- W371945
- Size
- 3/4
- Test gauge serial
- G-1616
- Gauge calibration date
- Feb 6, 2024
- Check valve 1
- 5.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-10-01153
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2706 Cedar Hollow Ln
Owner: Sam Brandt
Parcel 041-10-01153