Backflow assembly test · Two Rivers Self Storage
ApprovedFiled Aug 25, 2026 by Casey Fairley, Heritage Backflow Testing · filed from phone
Report
- Date of service
- Aug 25, 2026
- Assembly type
- RP
- Serial number
- A377287
- Size
- 2
- Test gauge serial
- G-9764
- Gauge calibration date
- Jun 7, 2026
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-61-01138
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2219 Cedar Hollow Dr
Owner: Okafor Holdings LLC
Parcel 041-61-01138