Marin County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 1999 Laurel Ln

Approved

Filed May 21, 2025 by Quinn Nguyen, Northstar Backflow Testing · filed from phone

Report

Date of service
May 21, 2025
Assembly type
DC
Serial number
W500932
Size
3/4
Test gauge serial
G-2864
Gauge calibration date
Feb 1, 2024
Check valve 1
9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-33-01300
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1999 Laurel Ln
Owner: Quinn Harlow
Parcel 041-33-01300