Marin County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Medical Offices

Filed Nov 20, 2026 by Casey Fairley, Heritage Backflow Testing · filed from phone

Report

Date of service
Nov 20, 2026
Assembly type
DC
Serial number
Z802682
Size
1
Test gauge serial
G-9800
Gauge calibration date
Aug 5, 2025
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
2.1 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-18-01056
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Property

4919 Old Church Trl
Owner: Benton Holdings LLC
Parcel 041-18-01056