Backflow assembly test · 5427 Quarry Rd
ApprovedFiled Jul 19, 2026 by Casey Fairley, Heritage Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Jul 19, 2026
- Assembly type
- PVB
- Serial number
- W151852
- Size
- 3/4
- Test gauge serial
- G-9714
- Gauge calibration date
- Jul 19, 2025
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-40-01124
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
5427 Quarry Rd
Owner: Shawn Hollins
Parcel 041-40-01124