Backflow assembly test · 2592 Pine Knoll Trl
ApprovedFiled May 7, 2024 by Drew Kessler, Heritage Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- May 7, 2024
- Assembly type
- RP
- Serial number
- A624684
- Size
- 3/4
- Test gauge serial
- G-2596
- Gauge calibration date
- Nov 14, 2023
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 037-68-01176
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2592 Pine Knoll Trl
Owner: Jordan Ramirez
Parcel 037-68-01176