← Backflow review queue
Backflow assembly test · 9142 Mill Creek Rd
ApprovedFiled Feb 14, 2026 by Parker Vance, Valley Backflow Testing · filed from phone
Report
- Date of service
- Feb 14, 2026
- Assembly type
- RP
- Serial number
- W990085
- Size
- 1
- Test gauge serial
- G-8753
- Gauge calibration date
- Sep 7, 2025
- Check valve 1
- 3.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 1.8 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 037-13-01222
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9142 Mill Creek Rd
Owner: Blake Calloway
Parcel 037-13-01222