Los Angeles County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Bakery

Approved

Filed Dec 9, 2025 by Parker Whitcomb, Ridge Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Dec 9, 2025
Assembly type
RP
Serial number
K804861
Size
4
Test gauge serial
G-5756
Gauge calibration date
Feb 22, 2025
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 037-95-01204
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8685 Old Church Dr
Owner: Danner Holdings LLC
Parcel 037-95-01204