Los Angeles County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Bakery

Approved

Filed Dec 12, 2024 by Parker Whitcomb, Ridge Backflow Testing · filed from phone

Report

Date of service
Dec 12, 2024
Assembly type
RP
Serial number
K804861
Size
4
Test gauge serial
G-1659
Gauge calibration date
Jul 13, 2024
Check valve 1
4.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 037-95-01204
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

8685 Old Church Dr
Owner: Danner Holdings LLC
Parcel 037-95-01204