Los Angeles County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Hilltop Self Storage

Approved

Filed Dec 1, 2025 by Parker Whitcomb, Ridge Backflow Testing · filed from phone

Report

Date of service
Dec 1, 2025
Assembly type
RP
Serial number
A925810
Size
1 1/2
Test gauge serial
G-1231
Gauge calibration date
Feb 16, 2025
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 037-89-01073
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

618 Old Church Dr
Owner: Nguyen Holdings LLC
Parcel 037-89-01073