Los Angeles County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Hilltop Medical Offices

Approved

Filed Jan 15, 2026 by Parker Whitcomb, Ridge Backflow Testing · filed from phone

Report

Date of service
Jan 15, 2026
Assembly type
RP
Serial number
W383564
Size
4
Test gauge serial
G-2063
Gauge calibration date
Sep 14, 2025
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 037-48-01094
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4195 Spring Branch Dr
Owner: Hollins Holdings LLC
Parcel 037-48-01094