Backflow assembly test · 2072 Stone Gate Dr
ApprovedFiled Feb 3, 2024 by Reese Fairley, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Feb 3, 2024
- Assembly type
- PVB
- Serial number
- K411126
- Size
- 3/4
- Test gauge serial
- G-2763
- Gauge calibration date
- Aug 28, 2023
- Check valve 1
- 3.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-47-01051
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2072 Stone Gate Dr
Owner: Avery Danner
Parcel 025-47-01051