Backflow assembly test · 748 Mill Creek Way
ApprovedFiled Jan 14, 2025 by Reese Fairley, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Jan 14, 2025
- Assembly type
- DC
- Serial number
- W947412
- Size
- 1
- Test gauge serial
- G-1274
- Gauge calibration date
- Apr 29, 2024
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-33-01055
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.