Backflow assembly test · Main Street Diner
ApprovedFiled Apr 28, 2026 by Emerson Hollins, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Apr 28, 2026
- Assembly type
- RP
- Serial number
- A407861
- Size
- 4
- Test gauge serial
- G-6398
- Gauge calibration date
- Mar 19, 2026
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-13-01011
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1008 Mill Creek Ln
Owner: Benton Holdings LLC
Parcel 025-13-01011