← Backflow review queue
Backflow assembly test · 123 Quarry Ln
ApprovedFiled Dec 21, 2025 by Drew Stroud, Ridge Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Dec 21, 2025
- Assembly type
- RP
- Serial number
- A542036
- Size
- 1
- Test gauge serial
- G-6065
- Gauge calibration date
- Nov 16, 2025
- Check valve 1
- 4.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-61-01270
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
123 Quarry Ln
Owner: Drew Whitcomb
Parcel 025-61-01270