← Backflow review queue
Backflow assembly test · 5058 Meadow Lark Ln
ApprovedFiled Jan 7, 2026 by Drew Stroud, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Jan 7, 2026
- Assembly type
- RP
- Serial number
- W378063
- Size
- 3/4
- Test gauge serial
- G-9364
- Gauge calibration date
- May 15, 2025
- Check valve 1
- 6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-57-01239
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
5058 Meadow Lark Ln
Owner: Hayden Harlow
Parcel 025-57-01239