Backflow assembly test · 6482 Meadow Lark Ln
ApprovedFiled Apr 27, 2026 by Hayden Marsh, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Apr 27, 2026
- Assembly type
- DC
- Serial number
- Z920363
- Size
- 1
- Test gauge serial
- G-3489
- Gauge calibration date
- Oct 22, 2025
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.2 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-44-01082
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
6482 Meadow Lark Ln
Owner: Drew Hollins
Parcel 025-44-01082