Backflow assembly test · 5329 Pine Knoll Way
ApprovedFiled Oct 10, 2025 by Drew Stroud, Ridge Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Oct 10, 2025
- Assembly type
- PVB
- Serial number
- A395191
- Size
- 1
- Test gauge serial
- G-9638
- Gauge calibration date
- Jul 19, 2024
- Check valve 1
- 0 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-19-01350
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.