El Dorado County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Blue Heron Grill

Approved

Filed Oct 18, 2024 by Riley Marsh, Valley Plumbing & Backflow · filed from phone

Report

Date of service
Oct 18, 2024
Assembly type
RP
Serial number
A241312
Size
1
Test gauge serial
G-8142
Gauge calibration date
Oct 11, 2023
Check valve 1
0.1 psid
Check valve 1 closed tight
No
Check valve 2
1.1 psid
Relief valve opened at
2.7 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 017-45-01193
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1567 Meadow Lark Way
Owner: Lindqvist Holdings LLC
Parcel 017-45-01193