Backflow assembly test · Corner Car Wash
ApprovedFiled Sep 10, 2024 by Parker Stroud, Valley Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Sep 10, 2024
- Assembly type
- RP
- Serial number
- W511526
- Size
- 2
- Test gauge serial
- G-3523
- Gauge calibration date
- Jun 26, 2024
- Check valve 1
- 9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 017-61-01003
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
3963 Hickory Rd
Owner: Ashby Holdings LLC