Backflow assembly test · 3610 Cedar Hollow Way
ApprovedFiled Nov 5, 2024 by Avery Ashby, Summit Backflow Testing · filed from phone
Report
- Date of service
- Nov 5, 2024
- Assembly type
- DC
- Serial number
- W668806
- Size
- 3/4
- Test gauge serial
- G-2063
- Gauge calibration date
- Jun 23, 2024
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 017-72-01219
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.