Contra Costa County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Grill

Approved

Filed Apr 29, 2026 by Casey Benton, Patriot Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Apr 29, 2026
Assembly type
RP
Serial number
A519888
Size
1 1/2
Test gauge serial
G-7443
Gauge calibration date
Jul 16, 2025
Check valve 1
3.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-11-01127
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

6463 Mill Creek Dr
Owner: Nguyen Holdings LLC
Parcel 013-11-01127