Contra Costa County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 5236 Hickory Trl

Approved

Filed Jul 12, 2024 by Morgan Vance, Patriot Backflow Testing · filed from phone

Report

Date of service
Jul 12, 2024
Assembly type
RP
Serial number
A197888
Size
3/4
Test gauge serial
G-1948
Gauge calibration date
Feb 29, 2024
Check valve 1
4.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-94-01171
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5236 Hickory Trl
Owner: Blake Ashby
Parcel 013-94-01171