Backflow assembly test · 2498 Laurel Ct
ApprovedFiled Dec 18, 2025 by Casey Benton, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Dec 18, 2025
- Assembly type
- PVB
- Serial number
- Z757655
- Size
- 1
- Test gauge serial
- G-3514
- Gauge calibration date
- Oct 14, 2025
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-71-01207
- Readings in range, no flags
- Result: passing. Next due date resets when approved.