Contra Costa County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Station Bakery

Filed Nov 19, 2026 by Casey Benton, Patriot Backflow Testing · filed from phone

Report

Date of service
Nov 19, 2026
Assembly type
RP
Serial number
B482100
Size
1 1/2
Test gauge serial
G-6980
Gauge calibration date
Jun 23, 2026
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
2.1 psid
Relief valve opened at
3.9 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-31-01348
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Property

6812 Spring Branch Ln
Owner: Nguyen Holdings LLC
Parcel 013-31-01348