← Backflow review queue
Backflow assembly test · Station Bakery
Needs reviewFiled Nov 19, 2026 by Casey Benton, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Nov 19, 2026
- Assembly type
- RP
- Serial number
- B482100
- Size
- 1 1/2
- Test gauge serial
- G-6980
- Gauge calibration date
- Jun 23, 2026
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 3.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-31-01348
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Property
6812 Spring Branch Ln
Owner: Nguyen Holdings LLC
Parcel 013-31-01348