Backflow assembly test · 202 Meadow Lark Ct
ApprovedFiled Sep 27, 2024 by Casey Benton, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Sep 27, 2024
- Assembly type
- RP
- Serial number
- A313495
- Size
- 1
- Test gauge serial
- G-1498
- Gauge calibration date
- Feb 26, 2024
- Check valve 1
- 4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-97-01172
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.