← Backflow review queue
Backflow assembly test · 4234 Turkey Hill Trl
ApprovedFiled Oct 20, 2024 by Reese Benton, Summit Backflow Testing · filed from phone
Report
- Date of service
- Oct 20, 2024
- Assembly type
- RP
- Serial number
- Z420702
- Size
- 1
- Test gauge serial
- G-8734
- Gauge calibration date
- Feb 14, 2024
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-28-01180
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4234 Turkey Hill Trl
Owner: Sam Fairley
Parcel 009-28-01180