Calaveras County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7664 Laurel Ct

Approved

Filed Feb 19, 2025 by Emerson Marsh, Summit Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Feb 19, 2025
Assembly type
RP
Serial number
W261665
Size
1
Test gauge serial
G-5584
Gauge calibration date
Sep 13, 2024
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-20-01160
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7664 Laurel Ct
Owner: Reese Benton
Parcel 009-20-01160