Backflow assembly test · 6387 Turkey Hill Way
Needs reviewFiled Nov 18, 2026 by Sam Ellery, Summit Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Nov 18, 2026
- Assembly type
- RP
- Serial number
- K278239
- Size
- 3/4
- Test gauge serial
- G-8483
- Gauge calibration date
- Aug 7, 2026
- Check valve 1
- 0 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 3.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-71-01343
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Property
6387 Turkey Hill Way
Owner: Sam Ellery
Parcel 009-71-01343