ApprovedFiled Aug 22, 2025 by Blake Ellery, Valley Backflow Testing · filed from phone
Report
- Date of service
- Aug 22, 2025
- Assembly type
- DC
- Serial number
- A217048
- Size
- 1 1/2
- Test gauge serial
- G-6991
- Gauge calibration date
- Feb 23, 2025
- Check valve 1
- 3.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-23-01025
- Readings in range, no flags
- Result: passing. Next due date resets when approved.