Backflow assembly test · 6947 Pine Knoll Ln
ApprovedFiled Oct 15, 2025 by Reese Benton, Summit Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Oct 15, 2025
- Assembly type
- PVB
- Serial number
- B694480
- Size
- 3/4
- Test gauge serial
- G-2586
- Gauge calibration date
- Aug 21, 2025
- Check valve 1
- 4.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-72-01090
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
6947 Pine Knoll Ln
Owner: Taylor Hollins
Parcel 009-72-01090