Back to the backflow review queue

Backflow assembly test: 2912 Sycamore Dr

Approved

Filed Dec 30, 2025 by Rowan Marsh, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 30, 2025
Assembly type
RP
Serial number
W544031
Size
3/4
Test gauge serial
G-8704
Gauge calibration date
Oct 22, 2025
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Marsh, current on the service date
  • All required fields present
  • Address matches parcel 009-32-01170
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2912 Sycamore Dr
Owner: Hayden Ellery
Parcel 009-32-01170