← Backflow review queue
Backflow assembly test · 2912 Sycamore Dr
ApprovedFiled Nov 27, 2024 by Logan Kessler, Valley Backflow Testing · filed from phone
Report
- Date of service
- Nov 27, 2024
- Assembly type
- RP
- Serial number
- W544031
- Size
- 3/4
- Test gauge serial
- G-3643
- Gauge calibration date
- Dec 3, 2023
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 3.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-32-01170
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2912 Sycamore Dr
Owner: Hayden Ellery
Parcel 009-32-01170