Calaveras County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 9676 Sycamore Dr

Approved

Filed Aug 23, 2026 by Avery Pruitt, Valley Backflow Testing · filed from phone

Report

Date of service
Aug 23, 2026
Assembly type
RP
Serial number
A986127
Size
3/4
Test gauge serial
G-8133
Gauge calibration date
Apr 7, 2026
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-53-01351
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

9676 Sycamore Dr
Owner: Cameron Pruitt
Parcel 009-53-01351