← Backflow review queue
Backflow assembly test · Corner Animal Hospital
ApprovedFiled Aug 10, 2026 by Rowan Marsh, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Aug 10, 2026
- Assembly type
- RP
- Serial number
- Z760732
- Size
- 1 1/2
- Test gauge serial
- G-1232
- Gauge calibration date
- Nov 2, 2025
- Check valve 1
- 5.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-36-01213
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
5645 Ridgeview Way
Owner: Hollins Holdings LLC
Parcel 009-36-01213