Backflow assembly test · 9244 Quarry Trl
ApprovedFiled Oct 25, 2026 by Avery Ellery, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Oct 25, 2026
- Assembly type
- PVB
- Serial number
- A575246
- Size
- 3/4
- Test gauge serial
- G-8843
- Gauge calibration date
- Jan 24, 2026
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-62-01286
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9244 Quarry Trl
Owner: Casey Nguyen
Parcel 001-62-01286