Alameda County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2614 Turkey Hill Trl

Approved

Filed Feb 18, 2026 by Rowan Okafor, Ridge Backflow Testing · filed from phone

Report

Date of service
Feb 18, 2026
Assembly type
DC
Serial number
Z492332
Size
3/4
Test gauge serial
G-8314
Gauge calibration date
Dec 22, 2024
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-26-01080
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2614 Turkey Hill Trl
Owner: Morgan Wexler
Parcel 001-26-01080