Backflow assembly test · Corner Elementary School

Approved

Filed Sep 7, 2026 by Quinn Nguyen, Keystone Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Sep 7, 2026
Assembly type
RP
Serial number
K614381
Size
4
Test gauge serial
G-1418
Gauge calibration date
Feb 14, 2026
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-18-01245
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.