Backflow assembly test · 3974 Orchard Trl
ApprovedFiled Apr 11, 2024 by Alex Benton, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- Apr 11, 2024
- Assembly type
- RP
- Serial number
- B882799
- Size
- 1
- Test gauge serial
- G-8124
- Gauge calibration date
- Jul 16, 2023
- Check valve 1
- 6.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-94-01114
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.