← Backflow review queue

Backflow assembly test · Corner Apartments

Approved

Filed Sep 18, 2024 by Casey Danner, Lakeside Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Sep 18, 2024
Assembly type
RP
Serial number
B961319
Size
1
Test gauge serial
G-8536
Gauge calibration date
Jun 22, 2024
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 143-55-01030
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.