Backflow assembly test · 7204 Quarry Dr
ApprovedFiled Feb 14, 2026 by Jamie Ashby, Summit Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Feb 14, 2026
- Assembly type
- DC
- Serial number
- A153704
- Size
- 3/4
- Test gauge serial
- G-2586
- Gauge calibration date
- Sep 18, 2025
- Check valve 1
- 5.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 143-16-01350
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.