Backflow assembly test · 9396 Spring Branch Trl
ApprovedFiled Jun 9, 2026 by Taylor Pruitt, Summit Backflow Testing · filed from phone
Report
- Date of service
- Jun 9, 2026
- Assembly type
- RP
- Serial number
- A725238
- Size
- 3/4
- Test gauge serial
- G-6342
- Gauge calibration date
- Apr 16, 2026
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 143-64-01326
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.