ApprovedFiled Oct 22, 2023 by Taylor Pruitt, Summit Backflow Testing · filed from phone
Report
- Date of service
- Oct 22, 2023
- Assembly type
- DC
- Serial number
- Z119707
- Size
- 3/4
- Test gauge serial
- G-2707
- Gauge calibration date
- Feb 9, 2023
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 143-80-01333
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.